Question of the Day for Monday, 16 November 2026
ASP · Fire Prevention and Protection
At a utility substation, the estimate for a 480 V panel task is 1.6 cal/cm2, and nothing in the work area could ignite clothing or spatter molten metal. A technician arrives in a 65/35 polyester and cotton work shirt that has not been treated. Under 29 CFR 1910.269, what is required?
Explanation
Paragraph (l)(8)(iii) bars clothing that could melt onto the skin or ignite and keep burning at the estimated energy, and its note names polyester blends unless treated, so the shirt must go at any estimate. Arc-rated clothing under (l)(8)(v) and a flame-resistant outer layer under (l)(8)(iv)(D) are triggered only when the estimate exceeds 2.0 cal/cm2, so neither is required at 1.6. The voltage trigger for a flame-resistant outer layer is contact with parts above 600 volts, not 50 volts. Source: 29 CFR 1910.269(l)(8)(iii) to (v).Practise more questions like this