ASP practice question: Electrical principles

Question of the Day for Wednesday, 4 November 2026

ASP · Safety Programs and Concepts
A 120-volt branch circuit protected by a 20-ampere breaker feeds a metal-cased bench grinder at a fabrication shop. The hot conductor faults to the grinder's case. Which ground-fault return path impedance would leave the case energized without tripping the breaker?

Explanation

Fault current is I = V/Z, so an 8-ohm path carries only 120/8 = 15 A, below the 20 A breaker rating, and the grinder case stays energized at a dangerous voltage. The 2.0-ohm path is the most tempting answer because a loose fitting sounds unsafe, but it still drives 60 A, three times the breaker rating, so the breaker opens. The 0.3 and 1.0 ohm paths drive 400 A and 120 A and trip the breaker quickly, which is why the ground path must be permanent, continuous and effective. Source: 29 CFR 1910.304(g)(5) and FAA-H-8083-30B, Aviation Maintenance Technician Handbook General (2023), Chapter 12, Fundamentals of Electricity and Electronics (Ohm's law).